Three-Phase Power and Why the Square Root of Three Appears

Finds three-phase power as P = √3 × line voltage × line current × power factor. The √3 appears because the line voltage is √3 times the phase voltage. The apparent and reactive powers are given as well.

This finds the power in a three-phase alternating supply, the form in which nearly all industrial and large-building machinery is fed.

P=3VIcosϕP = \sqrt{3} \, V I \cos\phi

Here VV is the line voltage, II the line current, cosϕ\cos\phi the power factor and PP the real power.

Where the square root of three comes from

A three-phase supply carries three voltages 120 degrees apart. The line voltage, measured between any two lines, is 3\sqrt{3} times the phase voltage of a single leg. Because the two voltages being subtracted are 120 degrees out of step, the difference is not simply double but 3\sqrt{3} times one of them.

The power in three legs is 3VpIcosϕ3 V_p I \cos\phi, and substituting Vp=V/3V_p = V / \sqrt{3} leaves 3/3=33 / \sqrt{3} = \sqrt{3}, which is the formula above.

Worked example

A line voltage of 200 V, a line current of 10 A and a power factor of 0.8 give about 2771 W of real power.

The apparent power is 3×200×10=3464\sqrt{3} \times 200 \times 10 = 3464 VA, and multiplying by the power factor of 0.8 leaves 2771 W. The reactive power is 3464×0.6=20783464 \times 0.6 = 2078 var, and the phase voltage is 200 ÷ 1.732 = 115.5 V.

Points to watch

The voltage and current here are the line values. Entering phase values instead puts the answer out by a factor of 3\sqrt{3}.

The formula assumes a balanced load, with the three phases loaded equally. An unbalanced load has to be worked out phase by phase.